BESS State of Health: Usable-Capacity Testing, SOH Calculation and Degradation Tracking

Battery energy storage systems lose usable energy and power capability as cells age. State of health (SOH) is intended to describe that decline, but a single percentage can be misleading unless the reference condition, test boundaries and calculation method are defined. A defensible capacity test controls temperature, power, state-of-charge endpoints and auxiliary loads so results can be compared over time.
Core rule: SOH is a ratio to a documented reference. If the test power, temperature, voltage limits, balancing state or measurement boundary changes, the new percentage may not represent real degradation.
SoC, SOH and efficiency are different
| Metric | Question answered |
|---|---|
| State of charge (SoC) | How full is the battery now? |
| Capacity SOH | How much usable energy remains compared with the reference? |
| Power SOH | Can the battery still deliver the required kW or MW within limits? |
| Round-trip efficiency | How much discharged energy is recovered relative to charged energy? |
| Availability | How often is the system ready when requested? |
A battery can show 100% SoC while having only 85% of its original usable capacity.
Define the measurement boundary
Capacity can be measured at several points:
- Cell DC terminals.
- Rack or container DC bus.
- PCS DC terminals.
- AC point of interconnection.
Each boundary includes different losses. AC-delivered energy includes inverter, transformer, cable and possibly auxiliary losses. Never compare DC nameplate energy directly with AC export without adjusting the boundary.
Basic capacity SOH
A simple ratio is:
SOHcapacity = Emeasured / Ereference × 100%
If a system delivered 8.4 MWh under the defined test and the accepted beginning-of-life reference is 10.0 MWh at the same boundary:
SOHcapacity = 8.4 / 10.0 × 100% = 84%
The calculation is easy; making the two energy values genuinely comparable is the difficult part.
Rated energy versus usable energy
Nameplate energy may represent nominal cell energy over a broad voltage range. The warranty or dispatch system may use a narrower SoC window, for example 10% to 90%, to protect life. Usable energy also depends on:
- Cell voltage limits.
- Minimum and maximum SoC.
- Temperature.
- Discharge rate.
- Inverter power limit.
- Weakest rack reaching a limit first.
- Balancing and calibration state.
Define the tested usable window explicitly.
Pre-test preparation
Before starting:
- Confirm the test procedure and warranty notice requirements.
- Verify all racks intended for the test are available.
- Review alarms, cell voltage spread and temperature spread.
- Complete balancing if required by the manufacturer.
- Calibrate revenue or test meters where needed.
- Stabilise battery temperature within the target band.
- Freeze control settings, SoC limits and auxiliary mode.
- Confirm grid export/import permissions and dispatch schedule.
- Define abort conditions for temperature, voltage and communications.
Recommended test sequence
A typical usable-capacity test includes:
- Charge to the defined upper endpoint at the specified power.
- Hold or rest for the required period.
- Record starting SoC, cell-voltage spread and temperatures.
- Discharge at constant power to the defined lower endpoint.
- Integrate energy at the selected measurement boundary.
- Record which limit ended the test.
- Rest if required.
- Recharge to the original endpoint for round-trip efficiency.
Follow the battery supplier’s approved sequence; some chemistries or warranties require different rest or taper conditions.
Energy integration
Energy is the time integral of power:
E = ∫ P(t) dt
For sampled data:
E ≈ Σ Pi × Δt
If power is logged every second, use timestamp-aware integration and check for missing records. Do not multiply one average display value by the nominal duration when the system curtailed or ramped.
Worked test example
Assume a BESS has a 10.0 MWh beginning-of-life AC usable-energy reference. During an annual test:
- Discharge power command: 2.5 MW.
- Measured AC energy exported: 8.65 MWh.
- A 0.10 MWh data-quality correction is rejected because the meter record is incomplete.
- Accepted measured energy: 8.65 MWh.
Capacity SOH is:
SOH = 8.65 / 10.0 × 100% = 86.5%
At constant 2.5 MW, the discharge lasted about:
8.65 / 2.5 = 3.46 h
If the contract requires 4 hours at 2.5 MW, the system cannot meet the full 10 MWh duty without augmentation, reduced power or a changed operating window.
Temperature normalisation
Low temperature can reduce available power and energy temporarily; high temperature changes resistance and ageing. If the reference is specified at 25°C but the annual test averages 15°C, direct comparison can understate SOH. Use the supplier’s validated temperature correction or repeat the test in the specified band. Do not invent a universal correction factor across chemistries.
C-rate and power dependence
The same battery can deliver different energy at 0.25C and 1C because of voltage drop, heating and control limits. Test at the contractual power or apply a manufacturer-approved correction. State the MW and effective C-rate in every SOH report.
Which limit ended the test?
The reason for termination is diagnostic:
- Minimum system SoC.
- Lowest cell voltage.
- Rack undervoltage.
- Maximum temperature.
- PCS power or current limit.
- Communications fault.
- Grid dispatch interruption.
If one weak rack hits voltage limit early, the system may leave substantial energy unused in healthier racks.
Cell and rack spread
Trend before and after test:
- Maximum-minus-minimum cell voltage.
- Maximum-minus-minimum cell temperature.
- Rack SoC dispersion.
- Rack current sharing.
- Balancing activity.
- Internal-resistance indicators.
Increasing spread can predict future usable-capacity loss even when the present SOH remains acceptable.
Capacity SOH versus power SOH
A battery may retain energy but lose power capability because internal resistance has increased. Power SOH evaluates whether the system can meet the required power without reaching voltage or temperature limits. Useful indicators include:
- Voltage sag during a defined power step.
- DC resistance or pulse-power test.
- Maximum sustainable charge and discharge current.
- Thermal rise at contractual power.
- PCS clipping versus battery limitation.
Report energy and power capability separately.
Round-trip efficiency calculation
For the same boundary:
RTE = Edischarged / Echarged × 100%
If 9.50 MWh is imported and 8.65 MWh exported:
RTE = 8.65 / 9.50 × 100% = 91.1%
This is not SOH. A degraded battery can still have good RTE, and an efficient battery can have reduced capacity.
Auxiliary-load treatment
HVAC, pumps, controls and fire-safety systems consume energy. Decide whether the contract uses gross or net AC energy. A net test subtracts auxiliaries from exported energy or includes them in imported energy according to the defined boundary. Record ambient conditions because HVAC consumption can vary significantly.
SoC calibration errors
The BMS estimates SoC using current integration, voltage models and periodic calibration. Drift can make the displayed SoC window differ from actual usable energy. A full controlled cycle can recalibrate the estimate, but repeated deep cycles may add wear. Follow the supplier’s calibration strategy.
Degradation trend
Plot SOH versus equivalent full cycles, calendar time and cumulative energy throughput. A simple annual slope can hide important phases:
- Early stabilisation or formation effects.
- Approximately linear midlife decline.
- Faster end-of-life divergence among cells.
Compare actual degradation with the warranted curve at matched conditions.
Equivalent full cycles
A common throughput metric is:
EFC = cumulative discharged energy / reference usable energy
Partial cycles contribute proportionally. EFC is useful but does not capture calendar ageing, temperature or time spent at high SoC.
Warranty comparison
Before declaring a warranty shortfall, confirm:
- Correct reference capacity and boundary.
- Allowed measurement uncertainty.
- Temperature and power correction.
- Required rack availability.
- SoC window and software version.
- Test notice and witness conditions.
- Excluded downtime or curtailment.
- Augmentation already included in the warranted baseline.
Measurement uncertainty
If power meters, CTs, voltage sensors and timestamps have uncertainty, the reported SOH should not imply false precision. Document meter class, calibration, data gaps and integration method. A result of 86.53% may reasonably support only 86.5% or 87% depending on the uncertainty budget.
Troubleshooting low measured capacity
| Observation | Possible causes |
|---|---|
| Early low-cell cutoff | Weak or imbalanced module |
| All racks end together at low energy | Real system-wide degradation or narrow SoC window |
| Low energy only in cold weather | Temperature effect or HVAC issue |
| Good DC energy, poor AC energy | PCS, transformer or auxiliary losses |
| Unequal rack currents | Cable resistance, contactor or control imbalance |
| SoC jumps near endpoint | Calibration or model mismatch |
Commissioning and annual report contents
- Asset configuration and available rack count.
- Software and parameter revisions.
- Test boundary and meter identifiers.
- Start/end SoC and voltage limits.
- Power profile and timestamps.
- Ambient and cell-temperature statistics.
- Charged and discharged energy.
- Net/gross auxiliary treatment.
- Capacity SOH, RTE and uncertainty.
- Limiting rack or cell.
- Comparison with prior tests and warranty curve.
Common mistakes
- Dividing AC export by DC nameplate energy.
- Comparing tests at different powers or temperatures.
- Calling RTE “battery health.”
- Ignoring unavailable racks in the denominator.
- Trusting displayed SoC without checking energy integration.
- Hiding the limit that ended the discharge.
- Reporting excessive decimal precision.
- Running a warranty test without following notification requirements.
Frequently asked questions
Is 80% SOH always end of life?
No. It is a common contractual threshold, but the usable end of life depends on the required duty, warranty and augmentation strategy.
Can SOH be estimated without a full cycle?
Yes, using model-based resistance and partial-cycle data, but uncertainty may be higher. Periodic controlled capacity tests provide valuable calibration.
Does adding new racks reset system SOH?
No. Augmentation changes installed and usable energy, but the fleet now contains different ages. Report the baseline and cohort structure clearly.
Conclusion
BESS SOH is meaningful only when its reference and test conditions are controlled. Measure energy at a defined boundary, normalise temperature and power, record the limiting condition and separate capacity, power and efficiency. Consistent annual tests turn one percentage into a reliable degradation trend and a practical augmentation decision.
This article is educational engineering guidance. Follow the battery supplier’s approved procedure, warranty conditions and site safety rules.