Overcurrent Relay Coordination: TCC Curves and Grading Margins

Coordinate overcurrent protection using pickups, inverse curves, grading margins and damage limits.
Protection principles
- Plot protective curves with inrush, motor start, cable withstand and damage limits.
- Pickup must exceed permissible load yet detect the minimum fault.
- Grading includes breaker opening, relay tolerance, overtravel and CT error.
- Validate maximum and minimum network configurations and installed settings.
Study workflow
Start from the current single-line diagram, verified equipment data and maximum and minimum fault studies. Coordinate primary and backup protection while preserving sensitivity, selectivity, speed and security.
Commissioning checklist
Confirm CT and VT polarity, ratios and grounding; compare installed settings with the approved study; inject representative faults; verify trip matrices and event records; and document test equipment and tolerances.
Common mistake
Do not copy settings from another feeder. Network topology, fault level, breaker time, instrument transformers and equipment withstand are site-specific.
Featured photo by Emmanuel Ikwuegbu on Unsplash.



