Engineering Unit Conversion Checklist: SI, kW, kVA and Per-Unit

Quick answer: Preserve units through every calculation, convert once at a defined boundary and verify dimensions before trusting the number. Most serious conversion mistakes come from hidden prefixes, area or volume factors, absolute versus relative temperature, and confusing power with energy.

Use a controlled conversion workflow
- Write the source value exactly with its unit and prefix.
- Convert to one coherent unit system before applying the equation.
- Keep conversion factors visible as fractions that cancel.
- Carry enough precision through intermediate steps.
- Check the final dimension and order of magnitude.
SI prefixes that cause errors
| Prefix | Symbol | Factor |
|---|---|---|
| milli | m | 10−3 |
| micro | µ | 10−6 |
| kilo | k | 103 |
| mega | M | 106 |
| giga | G | 109 |
Case matters: mW is milliwatt, MW is megawatt. Avoid invented plural symbols and do not combine prefixes, such as “mµ.”
Power is not energy
A 2 MW load operating for 3 h uses 6 MWh, not 6 MW. In SI base units, 1 Wh = 3,600 J. When comparing a battery’s MWh rating with a MW demand, duration is energy divided by power only after efficiency and usable limits are defined.
kW, kVA and kvar
These are different quantities, not alternative labels. Active power P is kW, apparent power S is kVA, and reactive power Q is kvar. For the same operating point, PF = P/S. A 500 kVA transformer does not supply 500 kW at every power factor or temperature.
Area and volume conversions
Linear conversion factors must be squared or cubed. Because 1 m = 1,000 mm, 1 m² = 1,000,000 mm² and 1 m³ = 1,000,000,000 mm³. A conductor cross-section of 240 mm² equals 240 × 10−6 m², not 0.240 m².
Temperature: value versus difference
T(K) = t(°C) + 273.15 for absolute temperature. A temperature difference of 10 °C equals 10 K; do not add 273.15 to a difference. Fahrenheit conversions require both scale and offset.
Worked conversion example
A cable resistance is given as 0.075 Ω/km and the route length is 180 m. Convert length: 180 m × (1 km/1,000 m) = 0.180 km. One-way resistance is 0.075 × 0.180 = 0.0135 Ω. If the circuit formula requires loop length or temperature-corrected resistance, apply those separately and label them; do not hide them inside the unit conversion.
Per-unit conversion
Per-unit quantity = actual quantity/base quantity. Base selections must be stated. For a three-phase system with base apparent power Sb and line-to-line voltage Vb, base impedance is Zb = Vb²/Sb when coherent units are used. For example, 11 kV and 10 MVA give Zb = 11²/10 = 12.1 Ω because kV²/MVA reduces consistently to ohms.
When changing per-unit impedance from an old base to a new base, document both voltage and power bases. A percent impedance is per-unit multiplied by 100.
Spreadsheet safeguards
- Put units in dedicated headers, not only comments.
- Lock conversion cells and name base quantities.
- Use data validation for unit choices.
- Add an independent check using a different formulation.
- Test zero, nominal and extreme inputs.
- Prevent mixed decimal separators in imported data.
FAQ
Can units be removed after converting to SI?
No. Keep them visible until dimensional cancellation is proven.
How many decimals should be reported?
Match measurement uncertainty and design purpose; extra calculator digits are not extra accuracy.
Is per-unit dimensionless?
Yes, but its meaning depends on the documented base quantities.