Transformer Differential Protection: Inrush Restraint and CT Matching

Understand transformer differential protection, vector compensation, CT errors and inrush restraint.
Protection principles
- Represent transformer ratio, vector group and tap range correctly.
- Percentage restraint helps maintain stability during heavy external faults.
- Inrush logic must reflect waveform behavior rather than one rule of thumb.
- Test polarity, balanced load, tap extremes, CT saturation and trip logic.
Study workflow
Start from the current single-line diagram, verified equipment data and maximum and minimum fault studies. Coordinate primary and backup protection while preserving sensitivity, selectivity, speed and security.
Commissioning checklist
Confirm CT and VT polarity, ratios and grounding; compare installed settings with the approved study; inject representative faults; verify trip matrices and event records; and document test equipment and tolerances.
Common mistake
Do not copy settings from another feeder. Network topology, fault level, breaker time, instrument transformers and equipment withstand are site-specific.